Flow Control Industries Main

Product Info - 2" HDP:

Differential Pressure Range
psi (kPa)
05 = 5-70 (35-483)
10 = 10-90 (69-621)
>90 - Contact Factory
Body Pressure Rating
psi (kPa)
H = 300 (2069)
(Standard)
>300 - Contact Factory
Service Hot or Chilled Water, Glycol
Weight 34 lbs / 15.4 kg
Actuation 90° Electric, Pneumatic
Max. Temperature 250°F (121°C)
Connection Female NPT
Rangeability 100:1
Body Brass
Internals Brass/304 SS
Seals EPR/EPDM
Shutoff ANSI B16-104
Leakage ANSI/ FCI 70-2-1998,
Class IV
 
Flow Control Main Page
DeltaPValve ®
2" HDP Drawing
DIMENSIONS (in/mm)
"A" "B" "C" "D" "E" "F"
101/2 / 267 10 / 254 613/16 / 173 83/8 / 213 47/16 / 113 1/2 / 13
2" HDP Pressure Independent Valve